Since 2005, 16 Years Fire Alarm System Suppression and Manufacturer&Whole Solution Designer
We supply whole fire alarm and suppression system include conventional fire alarm system, addressable fire alarm system, emergency light system, FM200 gas suppression system, fire pump, fire hose reel and cabinet.
  • Home
  • Products
    ASENWARE Conventional Fire Alarm System has obtained lpcb ce certificationconsists, The system has Conventional Fire Alarm Control Panel, Smoke Detector ,Heat Detector , Beam Smoke Detector,Entrance LED Indicator etc composed
    ASENWARE Addressable Fire Alarm Control System are intelligent system which are designed to make it suitable for most of applications. It’s user friendly functionality makes it suitable to program and configure the devices. 7 ” touchscreen display gives the information for fire alarm, trouble , supervisory and other related information all the time.This system fully complied with the requirement of EN 54-2 and EN 54-4.
    ASENWARE Wireless fire alarm system features: Can connect both wired and wireless detectors Each zone can connect up to 20 wireless detectors and 20 wired detectors
    ASENWARE Fire Pump Series provide fire departments or private users with the ability to pump from any water source.

    ASENWARE Centralized Monitoring Emergency Luminaire System is designed for managing, monitoring and controlling emergency lights automatically. 
    ASENWARE fire fighting telephone system is the special communication equipment for fire fighting
  • Project
  • Newsroom
  • About Us
  • Contact
  • Technical RFQ
LPCB approved addressable fire...
Home > Products > LPCB approved addressable fire alarm control system
LPCB Addressable Fire Alarm System Loop Isolator Module AW-D314 for fire alarm system
AW-D314 loop isolator (hereinafter referred to as AW-D314), mainly used to isolate a portion of a short circuit on the bus, other devices on the bus to ensure normal operation. Upon elimination of the...
  • AW-D314 loop isolator (hereinafter referred to as AW-D314), mainly used to isolate a portion of a short circuit on the bus, other devices on the bus to ensure normal operation. Upon elimination of the short circuit fault, AW-D314 can be isolated out their own part back into the system. It is worth noting: AW-D314 using the bus to facilitate the determination of the location of a short circuit.
  • Addressable Fire Alarm System Loop Isolator Module Feature:

    1) In the event of a short circuit isolates faulty parts of the loop
    2) Automatically resetting once the fault has cleared
    3) LED lights indicate status

  • Addressable Fire Alarm System Loop Isolator Technical parameters:


    Nominal Line Voltage ( VNOM) 24V
    Standby Current <3mA
    Capacity 32 devices
    Indicate Yellow (flashes when polling, illuminates in action.)
    Maximum Line Voltage ( VMAX) 28V
    Minimum Line Voltage ( VMIN) 16V
    Maximum voltage at which the device isolates ( VSOMAX) 11V
    Minimum voltage at which the device isolates ( VSOMIN) 8V
    Maximum voltage at which the device reconnects( VSC MAX) 4V
    Minimum voltage at which the device reconnects( VSC MIN) 1.4V
    Maximum rated continuous current with the switch closed ( IC MAX) 1A
    Maximum rated switching current ( IS MAX) 3A
    Maximum leakage current with the switch open ( ILMAX) 15mA
    Maximum series impedance with the switch closed( ZC MAX) 0.15Ω
    Operating Temperature -10℃~+55℃