    ASENWARE Fire Alarm Control System are intelligent system which are designed to make it suitable for most of applications. It’s user friendly functionality makes it suitable to program and configure the devices. 7 ” touchscreen display gives the information for fire alarm, trouble , supervisory and other related information all the
    time.This system fully complied with the requirement of EN 54-2 and EN 54-4.
    ASENWARE Fire Pump Series provide fire departments or private users with the ability to pump from any water source.
    The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 24 standard. 
    ASENWARE Centralized Monitoring Emergency Luminaire System is designed for managing, monitoring and controlling emergency lights automatically. 
    Asenware FP300 series is a LPCB addressable fire alarm system with one loop of 324 addressable points, comply with EN 54 standard.
    ASENWARE fire fighting telephone system is the special communication equipment for fire fighting
    ASENWARE Heat Detector is photo-electronic detector using a state-of-the-art optical sensing chamber. 
  • Project
  • Newsroom
  • About Us
  • Contact
  • Technical RFQ
Gas extinguishing control syst...
Home > Products > Gas extinguishing control system
Automatic Gas Extinguisher Control Panel AW-GEC2169
AW-GEC2169 with a new design, easy to operate, metal box opening and closing door with visible glass window, make the Panel running more safe,The automatic extinguisher control panel AW-GEC2169 is des...
  • The automatic extinguisher control panel AW-GEC2169 is designed execute European standards of EN54-2 and EN54-4 Fire Detection and Fire Alarm systems clause,and Control and Indicating Equipment EN12094-1 firefighting system standards.
    EN54-2 Fire detection and fire alarm systems  part 2: control and indicating equipment 
    EN54-4 Fire detection and fire alarm systems  part 4: power supply equipment 
    EN12094-1 Fixed firefighting systems - Components for gas extinguishing systems
    Requirements and test methods for electrical automatic control and delay devices
    AW-GEC2169 with a new design, easy to operate, metal box opening and closing door with visible glass window, make the Panel running more safe.
  • The AW-GEC2169 automatic gas fire extinguisher panel has the following features:

    Alarm input : two alarming zone signal input , 16 detectors could be connected to each zone
    EM valve output : control the output of EM valve.
    Panel output: line fault output / alarm output / fire extinguishing signal output/24VDC output
    Power output: resettable 24VDC output, 200mA current limit protection
    Automatic power switching: 220V AC power and standby battery power can be switched automatically.
    Three levels of access control (view, operation, settings)
    Fault detection with display: Real-time detect working condition of input, output, system, power, ground, fuse,and so on.
    Manually disable function: Manually disable the Panel functions and zones devices.
    Evacuation: Manually activate the fire alarm devices.
    Silence operation: Manual silence the horns alarm and panel buzzer .
    Delay time setting: You can manual set the Panel reseting time and Release delay time.
    Panel Security Protection : outside cabinet with Visible glass window of opening and closing door .
    tability: long-term rigorous testing before leaving the factory, the Panel is stable, safe and reliable;
  • AC INPUT 220VAC 50HZ +10%
    -15%
    DC OUTPUT at Power Board 24VDC (19V-28V) and 5VDC (4.9V-5.1V)
    Voltage for MCU 5V for power board MCU, 3.3V for others
    Current at 24VDC from PSE <450mA standby current
    Maximum current from PSE 1.4A except batteries charge
    Batteries current 1.85A maximum, current limited
    Auxiliary output 24VDC, 200 mA max, current limited
    Extinguishant release delay time Adjustable 0 to 60seconds(5 second steps)
    Imin, Imax.a and Imax.b according to EN54-2 Imin=340mA, Imax.a=424mA, Imax.b=1.4A
    Batteries 2*12V/ 2.3Ah sealed lead acid gel, self-regulated
    Battery replace Resistance 1.6Ω±10% if needed
    Battery low-voltage protection 21V
    The maximum and minimum electrical ratings for each input and output Detectots / zone lines: 15.2V-28V     Sounder lines:19-28V
    Fire protection/Fire routing lines:19-28V  Fault routing lines:18-28V
    Detectors wiring allowed each zone 16 points
    Max points (detector and MCP) per CIE 32 points
    Zone alarm current 6mA minimum/ 27mA maximum
    Sounder output 200mA maximum
    Fire routing/ Fault routing 200mA maximum each terminal
    Communication protocol 2 wires RS485 bus system
    EOL resistor for zone, inputs(Except for main power) and outputs 6.8K 1W
    Wires for 220V AC IN (recommended) 16AWG
    Wires connect power board to interface board (recommended) 20AWG
    Wire for main board wiring with interface board (recommended) 28AWG
    Fuse on power board 3A/ 250V Glass tube fuse 5*20(mm) Fast/quick blow
    Fuses on interface board(general outputs) 0.2A /250V Glass tube fuse 5*20(mm) Fast/quick blow [*5pcs]
    Fuse on interface board(Main Power) 2A/ 250V Ceramic tube fuse 5*20(mm) Slowly blow
    Fuse on interface board(EM valve) 1.5A/ 250V Glass tube fuse 5*20(mm) Fast/quick blow
    Environmental Class A temperature range: -5 to 40°C (23~104°F)
    Humidity: 5 to 95% RH, non-condensing
    Terminal blocks rating All terminals rated for 12 to18 AWG
    (0.75 to 2.5 mm2)
    Wires between interface board (Panel)and Detector  (recommended) 2-core shielded cable for 12 to18 AWG
    (0.75 to 2.5 mm2)