Since 2005, 16 Years Fire Alarm System Suppression and Manufacturer&Whole Solution Designer
We supply whole fire alarm and suppression system include conventional fire alarm system, addressable fire alarm system, emergency light system, FM200 gas suppression system, fire pump, fire hose reel and cabinet.
  • Home
  • Products
    ASENWARE Conventional Fire Alarm System has obtained lpcb ce certificationconsists, The system has Conventional Fire Alarm Control Panel, Smoke Detector ,Heat Detector , Beam Smoke Detector,Entrance LED Indicator etc composed
    ASENWARE Addressable Fire Alarm Control System are intelligent system which are designed to make it suitable for most of applications. It’s user friendly functionality makes it suitable to program and configure the devices. 7 ” touchscreen display gives the information for fire alarm, trouble , supervisory and other related information all the time.This system fully complied with the requirement of EN 54-2 and EN 54-4.
    ASENWARE Wireless fire alarm system features: Can connect both wired and wireless detectors Each zone can connect up to 20 wireless detectors and 20 wired detectors
    ASENWARE Fire Pump Series provide fire departments or private users with the ability to pump from any water source.

    ASENWARE Centralized Monitoring Emergency Luminaire System is designed for managing, monitoring and controlling emergency lights automatically. 
    ASENWARE fire fighting telephone system is the special communication equipment for fire fighting
  • Project
  • Newsroom
  • About Us
  • Contact
  • Technical RFQ
Two Wire Addressable fire alar...
Home > Products > Two Wire Addressable fire alarm control system
Addressable Heat and Smoke Detector Combination Detector AW-D103
Asenware AW-D103 is combination heat and smoke detector, it is an intelligent addressable detector, which can be configured with Asenware AW-FP100 Series Addressable Fire Alarm Control Panel.
  • Asenware AW-D103 is combination heat and smoke detector, it is an intelligent addressable detector, which can be configured with Asenware AW-FP100 Series Addressable Fire Alarm Control Panel. Each point (devices) can be given specific ID, which allows the panel to continuously monitor specific detector location (point). It reduces the maintenance cost and makes it easier to maintain the system. It provides fire signal when both conditions are satisfied which reduces the chances of false alarm. The heat sensing portion utilizes a proven thermistor for accurate and reliable heat detection.
  • Addressable Heat and Smoke Detector Combination Detector Features:

    • Addressable-analog communication
    • Low standby current for continuous monitoring(≤2.5mA)
    • Two-wire connection
    • Two LEDs (RED), blinks in normal condition and becomes steady during fire alarm condition.
    • Remote test from Panel

    Spacing
    Spacing of detector must be followed by standard EN 54 or NFPA 72. NFPA 72 suggests for low airflow application spacing of 9.1 m for ceiling height up to 3.15 m can be applicable. However, please follow the specific codes and local codes for specific applications.
  • Addressable Heat and Smoke Detector Combination Detector Technical parameters:

    Model No. AW-D103  
    D/C 1712
    Operating Voltage Range 18V-28V DC
    Alarm Current ≤3mA
    Work Current ≤2.5mA  
    Temperature -10℃ to 50℃
    Smoke Sensitivity 0.1-0.15dB/m
    Fix Temperature Range 57℃ A2R
    Rate of Rise Alarm 7.1℃/5S
    Standard Number Ref EN 54-5:2000
    Size 99.80mm
    Terminals Connection No 6: Remote Indicator+
    No 3: Remote Indic
    No 2: Loop IN+ 
    No 5: Loop IN-

     

    Smoke and Heat Detector Installation

    AW-D103 addressable detector use a separate base to simplify the installation and
    maintenance. For proper installation, terminal connections to be followed as shown
    below.


    *All dimensions are in mm