Since 2005, 16 Years Fire Alarm System Suppression and Manufacturer&Whole Solution Designer
We supply whole fire alarm and suppression system include conventional fire alarm system, addressable fire alarm system, emergency light system, FM200 gas suppression system, fire pump, fire hose reel and cabinet.
  • Home
  • Products
    ASENWARE Conventional Fire Alarm System has obtained lpcb ce certificationconsists, The system has Conventional Fire Alarm Control Panel, Smoke Detector ,Heat Detector , Beam Smoke Detector,Entrance LED Indicator etc composed
    ASENWARE Addressable Fire Alarm Control System are intelligent system which are designed to make it suitable for most of applications. It’s user friendly functionality makes it suitable to program and configure the devices. 7 ” touchscreen display gives the information for fire alarm, trouble , supervisory and other related information all the time.This system fully complied with the requirement of EN 54-2 and EN 54-4.
    ASENWARE Wireless fire alarm system features: Can connect both wired and wireless detectors Each zone can connect up to 20 wireless detectors and 20 wired detectors
    ASENWARE Fire Pump Series provide fire departments or private users with the ability to pump from any water source.

    ASENWARE Centralized Monitoring Emergency Luminaire System is designed for managing, monitoring and controlling emergency lights automatically. 
    ASENWARE fire fighting telephone system is the special communication equipment for fire fighting
  • Project
  • Newsroom
  • About Us
  • Contact
  • Technical RFQ
2100/2189 series Addressble Fi...
Home > Products > 2100/2189 series Addressble Fire Alarm System
AW-ATD2188 Addressable Heat Detector
AW-ATD2188 addressable heat detector is a mated product of the 2188/2100 series fire alarm control panels.
  • AW-ATD2188 addressable heat detector (Detector hereunder) is a mated product of the 2188/2100 series fire alarm control panels. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding.

    The detector realizes real-time acquisition of the in situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routing inspection, the detector indicator will blink.

    When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from the detector, and the detector indicator will light at the same time to indicate a fire alarm.

    The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.


  • Features:
    1. It can realize electronic coding and rewrite the address via coder in situ.
    1. Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation.
    1. It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
    2. Non-polarity, two-bus connection that ensures convenient installation and maintenance.
    1. Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
  • Parameters: 
    1. Executive standard: GB4715-2005;
    2. Operating voltage: 24V (pulse modulation);
    3. Operating current: <300uA (monitoring status) or <1.5mA (alarm status);
    4. Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status;
    5. Weight: about 47g;
    6. Product class: A2;
    7. External dimensions: diameter: 100mm, height: 56mm (with the base);
    8. Wiring method: non-polarity two-bus system (L1, L2);
    9. Operating environment: Indoor, temperature: 10℃~+50℃; relative humidity: ≤95% (40℃±2℃, without condensation);
    10. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection;
    11. Installation height: ≤8m;
    12. Protection area: about 60m². For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System;
    13. Matched host machine: fire alarm control panel (such as AW-AFP2188, AW-AFP2100).