    ASENWARE Fire Alarm Control System are intelligent system which are designed to make it suitable for most of applications. It’s user friendly functionality makes it suitable to program and configure the devices. 7 ” touchscreen display gives the information for fire alarm, trouble , supervisory and other related information all the
    time.This system fully complied with the requirement of EN 54-2 and EN 54-4.
    ASENWARE Fire Pump Series provide fire departments or private users with the ability to pump from any water source.
    The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 24 standard. 
    ASENWARE Centralized Monitoring Emergency Luminaire System is designed for managing, monitoring and controlling emergency lights automatically. 
    Asenware FP300 series is a LPCB addressable fire alarm system with one loop of 324 addressable points, comply with EN 54 standard.
    ASENWARE fire fighting telephone system is the special communication equipment for fire fighting
    ASENWARE Heat Detector is photo-electronic detector using a state-of-the-art optical sensing chamber. 
  • Project
  • Newsroom
  • About Us
  • Contact
  • Technical RFQ
LPCB approved conventional fir...
Home > Products > LPCB approved conventional fire alarm control system
2 Zone Fire Alarm Control Panel AW-CFP2166-2
The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke...
  • The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.

  • 1.Maximum number of Analogue Conventional Detector Inputs: 20 detectors each  zone
    2.Available Options: 2-4 Zone and 6-8 Zone
    3.4 outputs for Alarm devices: Includes 2 bells/fire relay/ fault relay
    4.Auxiliary resettable power output: 24VDC/ 100mA limiting protection
    5.Automatic power switchover: mains power and secondary power (from batteries)
    6.Independent functional buttons with indication: User friendly interface for easy operation and recognition
    7.Access levels to enter the panel
    8.Fault supervision and notification: inputs, outputs, system, power, earth, fuse
    9.Disablement: zones disablement
    10.Evacuation: Fire drills to simulate fire alarm condition on panel
    11.Silence: sounders and buzzer silence
    12.Walk test: indicators check

  • AC INPUT
     
    220VAC 50/60Hz
    +10%
        -15%
    DC OUTPUT 24VDC typical
    Voltage for MCU 5V for MCU
    Current at 24VDC from PSE 450mA standby current
    Maximum current from PSE 1A except batteries charge
    Batteries current 1.85A maximum, current limited
     
    Auxiliary output
    24VDC +/- 10%, 100 mA max,
    current limited, monitored
     
    Batteries
    2*12V/ 2.3Ah sealed lead acid gel,
    self-regulated *
    Battery low-voltage protection 21V
    Detectors connection allowed each zone 20 (except MCPs)
    Zone alarm current 6mA minimum/ 27mA maximum
    Sounder output 2*0.75A maximum
    Fire Relay 1A/30VDC maximum
    Fault Relay 1A/30VDC    maximum
    Communication protocol 2 wires RS485 bus system
    EOL resistor for zone 6.8K 1W
    EOL resistor for outputs 6.8K 1W
    Fuse for AC Power 1 A/ 250V glass tube fuse 5 X 20mm
    Fuse on DC Power 1A/ 250V glass tube fuse 5 X 20mm
     
    Environmental
    Class A temperature range: -5 to 40°C (23~104°F)
    Humidity: 5 to 95% RH, non-condensing
     
    Terminal blocks rating
    All terminals rated for 12 to18 AWG
    (0.75 to 2.5 mm2)