2100/2189 series Addressble Fire Alarm System
AW-ATD2188 Addressable Heat Detector
AW-ATD2188 addressable heat detector is a mated product of the 2188/2100 series fire alarm control panels.
Product overview

AW-ATD2188 addressable heat detector (Detector hereunder) is a mated product of the 2188/2100 series fire alarm control panels. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding.

The detector realizes real-time acquisition of the in situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routing inspection, the detector indicator will blink.

When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from the detector, and the detector indicator will light at the same time to indicate a fire alarm.

The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.


Product Features
Features:
  1. It can realize electronic coding and rewrite the address via coder in situ.
  1. Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation.
  1. It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
  2. Non-polarity, two-bus connection that ensures convenient installation and maintenance.
  1. Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
Technical parameters
Parameters: 
  1. Executive standard: GB4715-2005;
  2. Operating voltage: 24V (pulse modulation);
  3. Operating current: <300uA (monitoring status) or <1.5mA (alarm status);
  4. Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status;
  5. Weight: about 47g;
  6. Product class: A2;
  7. External dimensions: diameter: 100mm, height: 56mm (with the base);
  8. Wiring method: non-polarity two-bus system (L1, L2);
  9. Operating environment: Indoor, temperature: 10℃~+50℃; relative humidity: ≤95% (40℃±2℃, without condensation);
  10. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection;
  11. Installation height: ≤8m;
  12. Protection area: about 60m². For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System;
  13. Matched host machine: fire alarm control panel (such as AW-AFP2188, AW-AFP2100).
 
Download
BACK