wireless addressable smoke & heat detector is mainly designed for wireless control system. The detector most advanced optical sensing chamber and temperature sensing with the fastest response and highest
sensitivity. With wireless network alarm function, it can form a wireless local area network alarm system through the panel. Wireless connection, support for electronic coding, easy installation and construction.
2.Product Features
2.1 Easy to install, mounting bracket included
2.2 High quality durable sensor
2.3 Loud 85dB alarm and LED warning indicator
2.4 Excellent reliability and high stability
2.5 Suitable for all families and other places where needs
2.6 The battery is used for ten years, and it does not need to be replaced for ten years of normal operation.
2.7 Meets all requirements of latest EN standard Technical parameters
3. Technical Parameters
3.1 Operating voltage: 3VDC (with battery CR17450 / CR17455)
3.2 Operating current: monitoring status≤8uA, alarm status≤120mA
3.3 Operating Frequency: 433MHz (418MHz to 448MHz)
3.4 Wireless transmit power: +20dB
3.5 Smoke Alarm Sensitivity: 0.18-0.3dBM
3.6 Fix temperature Alarm:57°C (135°F) A2R
3.7 Rate of rise Alarm:≥10℃/2M A2R
3.8 Low battery alarm voltage:≤ 2.4V
3.9 The battery is used for ten years, and it does not need to be replaced for ten years of normal operation.
3.10 Battery Type: A Panasonic Corporation(Panasoic Energy Co.,Ltd)-CR17450/CR-AGF;B Huzhou Huiderui
Litium Battery Technology. Co,. Ltd)-CR17450.
3.11 Alarm SPL: ≥85dB @3m
3.12 Operating temperature: 0℃~40℃,Relative humidity: ≤93%(non-condensing)
3.13 Application: For indoor use only
3.14 Standard Number Ref:BS5446-2
3.15 Materials and colors: ABS, white
3.16 Size: φ105mm*105mm*50.2mm (Figure1)
3.17 Weight: about 120g
4. Mounting Base
AW-D605L should comply with all local codes. Shown in Figure 2, install the base of the AW-D605L on the wall.
And then insert the main body into the base.
The base dimensions of 105mm*105mm*41mm(Length*Width*Height),mounting hole diameter φ2mm, fixing the
hole spacing is 42mm, shown in Figure 3.
5. Operation
Test: When there is no fire alarm, you can press the test button to test. When pressed, both the buzzer and
LED light work intermittently (beep and LED blink)
Mute: When the detector is in the alarm state, press the button on the cover to mute the buzzer, the silence
period for each press is 5 minutes, and the longest does not exceed 15 minutes; if there is still a fire
alarm at the end of each silence period The alarm will be retriggered. Normal work: LED flashes once every 50 seconds and battery power is detected once, smoke density is
detected once every 4 seconds, and the buzzer does not sound. Low battery/failure: LED flashes once every 50 seconds, buzzer beeps once