Conventional Fire Alarm Control System LPCB Approved
4 Wire Conventional Smoke Detector with relay output
The AW-CSD381-4W conventional photo-electronic smoke detector uses a state of the art optical sensing chamber. This detector is designed to provide open area protection and to be used with the AW-CFP2166 conventional fire alarm panel and the panels from o
Product overview
The AW-CSD381-4W conventional photo-electronic smoke detector uses a state of the art optical sensing chamber. This detector is designed to provide open area protection and to be used with the AW-CFP2166 conventional fire alarm panel and the panels from other manufacturers.
The detector that initiated the alarm condition will have its red LED and relays latched until reset by panel.
Product Features
  • Surface mounting
  • LED indicator
  • Complete functional test with every activation
  • Meets all requirements of latest EN54-7:2001
Technical parameters
Technical Specification
Model AW-CSD381-4W
Main Voltage 9-60VDC
Operating current(@ 24VDC) NO Standby current≤120uA, Alarm current≤20mA
NC Standby current≤12mA, Alarm current≤5mA
Application For indoor use only
Wiring Terminal 6: DC Input      Terminal 5: DC Input
Terminal 3: Alarm output   Terminal 2: Alarm output
Protection class IP30
Smoke Alarm Sensitivity 0.18 to 0.3 dB/m
Environmental Class A temperature range: -10 to 50°C (14~122°F)
Humidity: 5 to 95% RH, non-condensing
Materials and colors ABS, White
Alarm relay output capacity 500mA @DC30V
Size φ99.8mm* 48.2mm
Weight About 114.5g