				 Detection Range  | 
			
				 Fire Source and Size  | 
			
				 Details  | 
		|
| 
				 
 Maximum Distance  | 
			
				 N-Heptane  | 
			
				 
 0.1m2 Fire plate  | 
			
				 40m  | 
		
| 
				 Gasoline  | 
			
				 35m  | 
		||
| 
				 Diesel  | 
			
				 35m  | 
		||
| 
				 Kerosene  | 
			
				 35m  | 
		||
| 
				 Alcohol  | 
			
				 30m  | 
		||
| 
				 Paper  | 
			
				 30m  | 
		||
| 
				 
 Methane  | 
			
				 
 H=0.5m W=0.3m  | 
			
				 
 30m  | 
		|
| 
				 Respond Time  | 
			
				 
 N-Heptane  | 
			
				 
 0.3*0.3m2  | 
			
				 
 <10s  | 
		
| 
				 Spectral range  | 
			
				 IR:4.3~5.0μM、UV:185~260nm  | 
		||
| 
				 Viewing angle range  | 
			
				 angle120°  | 
		||
| 
				 
 Detection distance  | 
			
				 Burning  | 
			
				 Fire source size  | 
			
				 Detection distance  | 
		
| 
				 N-heptane  | 
			
				 
 0.1m2Fire pan  | 
			
				 40m  | 
		|
| 
				 Gasoline  | 
			
				 35m  | 
		||
| 
				 Diesel oil  | 
			
				 35m  | 
		||
| 
				 Kerosene  | 
			
				 35m  | 
		||
| 
				 Alcohol  | 
			
				 30m  | 
		||
| 
				 Paper  | 
			
				 30m  | 
		||
| 
				 
 Methane  | 
			
				 Height0.5m Width0.2m  | 
			
				 
 30m  | 
		|
| 
				 
 Response time  | 
			
				 Fire source size  | 
			
				 
 Response time  | 
		|
| 
				 0.3m× 0.3mN-heptane flame  | 
			
				 
 ≤10S  | 
		||
| 
				 Sensitivity level  | 
			
				 Class I  | 
		||
| 
				 Voltage range  | 
			
				 DC24V(voltage range 18~30V)  | 
		||
| 
				 
 Working current  | 
			
				 ≤50mA(It has a working status indicator, which flashes green when it is under normal monitoring;It has a fire alarm confirmation light, which is always red when the fire alarm is in the state;It has a fault indicator light, which is always on when the fault state occurs)  | 
		|
| 
				 
 Relay output  | 
			
				 Fire alarm relay,1A@30VDC,Normally open contact output,Monitoring state normally open contact is disconnected,Fire alarm state normally open contact closed;  | 
		|
| 
				 Fault relay,1A@30VDC,Normally open contact output,Monitoring state normally open contact closed,Fault alarm state normally open contact is disconnected;  | 
		||
| 
				 Signal output  | 
			
				 Relay type  | 
			
				 2 fire alarm and fault relay output  | 
		
| 
				 Operation method  | 
			
				 Infrared remote control  | 
			
				 
  | 
		
| 
				 Reset method  | 
			
				 Power-off reset/communication protocol reset/remote control reset  | 
		|
| 
				 Operating temperature  | 
			
				 -40℃~70℃  | 
		|
| 
				 Storage temperature  | 
			
				 -40℃~85℃  | 
		|
| 
				 Working humidity  | 
			
				 0~96%RH (non-condensing) can withstand 100% condensing humidity for a short time  | 
		|
| 
				 Explosion-proof certification  | 
			
				 ExdⅡC T6 Gb/tD A21 IP66/IP67 T80℃  | 
		|
| 
				 Protection level  | 
			
				 IP66 /IP67  | 
		|
| 
				 Shell material  | 
			
				 Cast aluminum, surface paint  | 
		|
| 
				 Electrical Interface  | 
			
				 1×3/4NPT、M25*1.5 、G3/4 (Adapters can be customized according to requirements)  | 
		|
| 
				 Size  | 
			
				 120mm ×95mm ×85mm  | 
		
| 
				 Weight  | 
			
				 0.7KG  | 
		
| 
				 Accessories  | 
			
				 Cast aluminum bracket  | 
		
| 
				 
 Design standards  | 
			
				 GB 15631-2008 《Special fire detector》,GB 12791-2006《Point type UV flame detector》, GB3836《Explosive environment》  |