Wireless conventional fire alarm system
Wireless Temperature-sensing smoke composite battery detector SSTD606A
The detector is a photodetector that uses the most advanced optical sensing chamber. The detector is designed to provide open area protection and can be used with the AW-FP100 Series Addressable Fire Alarm Panel. It has a wireless network alarm function;
Product overview
The detector is a photodetector that uses the most advanced optical sensing chamber. The detector is designed to provide open area protection and can be used with the AW-FP100 Series Addressable Fire Alarm Panel. It has a wireless network alarm function; it can form a wireless LAN alarm system through the host; wireless connection, no wiring, easy installation and construction;
 
A bi-color LED on each detector provides a local 360° visible alarm indication. They flash once every minute to indicate that power is on and the detector is working properly. The red LED flashes when the alarm occurs. When there is a fault condition indicating that the detector sensitivity is outside the listed limits, the green LED will flash when the battery is low. The alarm can be reset by a host reset or when the fire alarm is not collected for a long time.
Startup fault After the green LED flashes, it can be reset until the fault is cleared through the panel;
 
The test button is used to test whether the detector works normally; each time the buzzer is pressed, the buzzer will respond with a drop, while the green LED flashes, sending a wireless communication signal with the host, the host will receive and display the detector test information; This button can be used for local silence during fire alarms;


Product Features
1.Easy To Install
   Easy to install and expand
 
2.Wireless
  Supporting Wireless Function with Host
 
3.High DB
   85 DB can better inform people
 
4.Double Battery Options
   Internal 3 /5/10 years battery External 1.5V 2PCS AA battery
Technical parameters
Working power:                                   A CR17335/17450 lithium manganese batteryB 2* AA alkaline battery 
Current:                                              ≤8µA@3VDC
Maximum Alarm Current (LED on):   ≤100mA@3VDC
Operating Humidity Range:               ≤95%RH(40°C±2°C) Relative Humidity, Non-condensing
Operating Temperature Range:          -10°C to 50°C (14°F to 122°F)
Smoke Alarm Sensitivity:                    0.18-0.26dBM
Fix temperature Alarm:                        57°C (135°F) A1R 
Rate of rise Alarm:                               7.1°C/5S  A1R
Wireless working frequency band:      428-438MHZ
Wireless transmit power                    +20DB
Alarm level:                                        ≥85db /3m
Height:                                                54.5mm installed in Base
Diameter:                                            126.7 mm