Wireless Temperature-sensing smoke composite battery detector SSTD606A                        
                        
                        	The detector is a photodetector that uses the most advanced optical sensing chamber. The detector is designed to provide open area protection and can be used with the AW-FP100 Series Addressable Fire Alarm Panel. It has a wireless network alarm function;                        
                        
                        
                     
                 
                
                    
                       
	The detector is a photodetector that uses the most advanced optical sensing chamber. The detector is designed to provide open area protection and can be used with the AW-FP100 Series Addressable Fire Alarm Panel. It has a wireless network alarm function; it can form a wireless LAN alarm system through the host; wireless connection, no wiring, easy installation and construction;
	 
	A bi-color LED on each detector provides a local 360° visible alarm indication. They flash once every minute to indicate that power is on and the detector is working properly. The red LED flashes when the alarm occurs. When there is a fault condition indicating that the detector sensitivity is outside the listed limits, the green LED will flash when the battery is low. The alarm can be reset by a host reset or when the fire alarm is not collected for a long time.
	Startup fault After the green LED flashes, it can be reset until the fault is cleared through the panel;
	 
	The test button is used to test whether the detector works normally; each time the buzzer is pressed, the buzzer will respond with a drop, while the green LED flashes, sending a wireless communication signal with the host, the host will receive and display the detector test information; This button can be used for local silence during fire alarms;
	 
                     
                 
                
                    
                       
	1.Easy To Install
	   Easy to install and expand
	 
	2.Wireless
	  Supporting Wireless Function with Host
	 
	3.High DB
	   85 DB can better inform people
	 
	4.Double Battery Options
	   Internal 3 /5/10 years battery External 1.5V 2PCS AA battery
                     
                 
                
                    
                        
	Working power:                                   A CR17335/17450 lithium manganese batteryB 2* AA alkaline battery 
	Current:                                              ≤8µA@3VDC
	Maximum Alarm Current (LED on):   ≤100mA@3VDC
	Operating Humidity Range:               ≤95%RH(40°C±2°C) Relative Humidity, Non-condensing
	Operating Temperature Range:          -10°C to 50°C (14°F to 122°F)
	Smoke Alarm Sensitivity:                    0.18-0.26dBM
	Fix temperature Alarm:                        57°C (135°F) A1R 
	Rate of rise Alarm:                               7.1°C/5S  A1R
	Wireless working frequency band:      428-438MHZ
	Wireless transmit power                    +20DB
	Alarm level:                                        ≥85db /3m
	Height:                                                54.5mm installed in Base
	Diameter:                                            126.7 mm