				AC INPUT | 
			
				220VAC 50HZ | 
			
				+10% | 
		
		
			| 
				-15% | 
		
		
			| 
				DC OUTPUT at Power Board | 
			
				24VDC (19V-28V) and 5VDC (4.9V-5.1V) | 
		
		
			| 
				Voltage for MCU | 
			
				5V for power board MCU, 3.3V for others | 
		
		
			| 
				Current at 24VDC from PSE | 
			
				<450mA standby current | 
		
		
			| 
				Maximum current from PSE | 
			
				1.4A except batteries charge | 
		
		
			| 
				Batteries current | 
			
				1.85A maximum, current limited | 
		
		
			| 
				Auxiliary output | 
			
				24VDC, 200 mA max, current limited | 
		
		
			| 
				Extinguishant release delay time | 
			
				Adjustable 0 to 60seconds(5 second steps) | 
		
		
			| 
				Imin, Imax.a and Imax.b according to EN54-2 | 
			
				Imin=340mA, Imax.a=424mA, Imax.b=1.4A | 
		
		
			| 
				Batteries | 
			
				2*12V/ 2.3Ah sealed lead acid gel, self-regulated | 
		
		
			| 
				Battery replace Resistance | 
			
				1.6Ω±10% if needed | 
		
		
			| 
				Battery low-voltage protection | 
			
				21V | 
		
		
			| 
				The maximum and minimum electrical ratings for each input and output | 
			
				Detectots / zone lines: 15.2V-28V     Sounder lines:19-28V 
				Fire protection/Fire routing lines:19-28V  Fault routing lines:18-28V | 
		
		
			| 
				Detectors wiring allowed each zone | 
			
				16 points | 
		
		
			| 
				Max points (detector and MCP) per CIE | 
			
				32 points | 
		
		
			| 
				Zone alarm current | 
			
				6mA minimum/ 27mA maximum | 
		
		
			| 
				Sounder output | 
			
				200mA maximum | 
		
		
			| 
				Fire routing/ Fault routing | 
			
				200mA maximum each terminal | 
		
		
			| 
				Communication protocol | 
			
				2 wires RS485 bus system | 
		
		
			| 
				EOL resistor for zone, inputs(Except for main power) and outputs | 
			
				6.8K 1W | 
		
		
			| 
				Wires for 220V AC IN (recommended) | 
			
				16AWG | 
		
		
			| 
				Wires connect power board to interface board (recommended) | 
			
				20AWG | 
		
		
			| 
				Wire for main board wiring with interface board (recommended) | 
			
				28AWG | 
		
		
			| 
				Fuse on power board | 
			
				3A/ 250V Glass tube fuse 5*20(mm) Fast/quick blow | 
		
		
			| 
				Fuses on interface board(general outputs) | 
			
				0.2A /250V Glass tube fuse 5*20(mm) Fast/quick blow [*5pcs] | 
		
		
			| 
				Fuse on interface board(Main Power) | 
			
				2A/ 250V Ceramic tube fuse 5*20(mm) Slowly blow | 
		
		
			| 
				Fuse on interface board(EM valve) | 
			
				1.5A/ 250V Glass tube fuse 5*20(mm) Fast/quick blow | 
		
		
			| 
				Environmental | 
			
				Class A temperature range: -5 to 40°C (23~104°F) 
				Humidity: 5 to 95% RH, non-condensing | 
		
		
			| 
				Terminal blocks rating | 
			
				All terminals rated for 12 to18 AWG 
				(0.75 to 2.5 mm2) | 
		
		
			| 
				Wires between interface board (Panel)and Detector  (recommended) | 
			
				2-core shielded cable for 12 to18 AWG 
				(0.75 to 2.5 mm2) |