Addressable Fire Alarm Control System LPCB Approved
Addressable Input Output Module AW-D319
Addressable Input Output  Module is used with AW-FP300 fire alarm control panel. It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers, blow valves and fire dampers) and receive the feedback
Product overview
The AW-D319 Addressable Input Output Module is used with AW-FP300 fire alarm control panel. It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers, blow valves and fire dampers) and receive the feedback signals of the fire linkage equipment so that a judgment on whether or not the fire linkage equipment is operating normally can be done.
 

How To Wire Input Output Module To Addressable Fire Alarm Control Panel

Product Features

LPCB Addressable Fire Alarm System Input Output Module Feature:

1. Executive standard: EN54-18
2. Operation voltage: loop DC24V (polarity-insensitive);power DC24V(polarity-insensitive)
3. Quiescent current: loop current<0.8mA; power current<2mA
4. Action current: loop current<5mA; power current<15mA
5. Capacity of the output control contact: 1A@DC30V
6. Operation indicator: The inspection indicator will blink once about every 12 seconds in the inspection status or remain lit in
the output status; the input indicator will remain lit in the feedback status.
7. Operating environment: Temperature: -10ºC ~ 55ºC; RH: ≤95% (40 ºC±2ºC, without condensation)
8. External dimensions: 86×86×41(mm,With base)
9. Weight: about 148g(With base)
Technical parameters

LPCB Addressable Fire Alarm System Input Output Technical parameters:


Operating Voltage
Signal Loop 24V(18V~28V)
Power 24VDC(20VDC~28VDC)
Standby Current Loop<0.8mA ; Power<2mA
Action Current Loop<5mA ; Power<15mA
Output Capacity 1A@DC30V
Input Mode Setting NC or NO input mode can be set by the jumper JP4.
Programming Method Electronically addressed
Code Range One address within 1~324.
 
Indicators
Inspection indicator: l blink once about every 12 seconds in the inspection status or remain lit in the output status;
Input indicator : remain lit in the feedback status.
Operating Temperature -10℃~+55℃
Relative Humidity ≤95% , non-condensing
Material of Enclosure ABS
 
Dimension (L×W×H)
86mm×86mm×41mm
(with base)
Mounting Hole Distance 60.5mm
Weight About 148g (with base)