Addressable Fire Alarm Control System LPCB Approved
LPCB Approved Addressable Fire Alarm Smoke Detector AW-D301
addressable photoelectric smoke detector (Detector hereunder) is a kind of photoelectric smoke detector. With an internal microprocessor, it supports electronic coding and is accessed through AW-FP300 fire alarm control panel via a two-wire bus. T
Product overview
addressable photoelectric smoke detector (Detector hereunder) is a kind of photoelectric smoke detector. With an internal microprocessor, it supports electronic coding and is accessed through AW-FP300 fire alarm control panel via a two-wire bus. The detector realizes real-time acquisition of the in situ smoke concentration data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel.
The detector is suitable for such industrial and civil buildings that have a great deal of smoke during fires but no smoke under normal circumstances, such as restaurants, hotels, teaching buildings, office buildings, computer rooms, communication machine rooms, libraries and archives. It is not suitable for places with a great deal of retained dust and water mist, places where steam and/or oil mist may be generated and places with retained smoke under normal circumstances.

How To Wire Addressable Smoke Detector

Product Features

Addressable Fire Alarm Smoke Detector Features:

1) It can realize electronic coding and rewrite the address via coder in situ.
2) Within a single-chip microcomputer, it can process the sampling data in real-time, save the latest 144 historical data and realize a curve tracing for the field situation.
3) It has a temperature, humidity and dust accumulation drift compensation function and a sensor fault detection function (fault reporting to fire alarm control panel)
4) Non-polarity, two-bus connection that ensures convenient installation and maintenance.
5) Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
6) Built-in remote indicator output terminal, drive remote indicator lit when fire alarm
Technical parameters

Addressable Fire Alarm Smoke Detector Technical parameters:


Operating Voltage Loop 24V(18V~28V)
Standby Current <0.3mA
Alarm Current <1.5mA (without remote indicator)
<3.5mA (with remote indicator)
Fire LED Red, Flash in polling, and illuminate in alarming.
Remote indicator output Polarity-sensitive output, directly connect to remote indicator (built in 10k
resistor in series, max. output current is 2mA); The red indicator will blink in the monitoring status or remain lit in the alarm status.
Programming Electronically addressed.
Programming Range Occupying one address within 1~324.
Wiring Loop: two wire, polarity-insensitive
Environmental Temperature -10℃~+55℃
Relative Humidity ≤95%, non-condensing
Material of Enclosure ABS
Dimension Diameter: 100mm
Height: 58mm (with the base)
Mounting Hole Distance 44.5mm~64.3mm
Weight About 128g(with base)
Operating Voltage Loop 24V(18V~28V)