Two Wire Addressable Fire Alarm Control System
Addressable Heat Detector AW-D102
Asenware AW-D102 heat detector is an intelligent rate of rise heat detector, which can be configured with Asenware AW-FP100 Series Addressable Fire Alarm Control Panel. Each point (devices) can be given specific ID
Product overview
Asenware AW-D102 heat detector is an intelligent rate of rise heat detector, which can be configured with Asenware AW-FP100 Series Addressable Fire Alarm Control Panel. Each point (devices) can be given specific ID, which allows the panel to continuously monitor specific detector location (point). It reduces the maintenance cost and makes it easier to maintain the system.

How To Wire Addressable Heat Detect To Addressable Fire Alarm Control Panel?

Product Features

Addressable Heat Detector Features:

• Addressable-analog communication
• Rate-of-rise feature activates when ambient temperature increases at the rate of 7.1 ℃/5S
• Low Standby current
• Two-wire connection
• Two LEDs (RED), blinks in normal condition and becomes stationary during fire alarm condition.
• Remote test from Panel

Spacing
Spacing of detector must be followed by standard EN 54 or NFPA 72. N FPA 72
suggests for low airflow application spacing of 9.1 m for ceiling height up to 3.15 m can
be applicable. However, please follow the specific codes and local codes for specific
applications.

Addressable Heat Detector Installation

AW-D102 addressable detector use a separate base to simplify the installation and
maintenance. For proper installation, terminal connections to be followed as shown
below.

Technical parameters
Model No. AW-D102 
D/C 1712
Operating Voltage Range 18V-28VDC 
Alarm Current ≤3mA
Work Current ≤2.5mA
Temperature -10℃ to 50℃
Fix Temperature Range 57℃ A2R
Rate of Rise Alarm 7.1℃/5S A2R
Standard Number Ref EN 54-5:2000
Size 99.80 mm
Terminals Connection No 6: Remote Indicator+  
No 3: Remote Indicator-
No 2: Loop IN+  
No 5: Loop IN-

 

Download