Design Parameters
On smooth ceilings installation, the distance between parallel detector runs shall not exceed the maximum listed spacing there, shall be a detector run within a distance of ½ listed spacing measured at a right angle from all walls or partitions that extend to within top 15% of the ceiling height.
On solid joist ceiling installations, with open joists or other similar structures heat travels freely down the joists channel, however heat has trouble spreading across the joists, so the distance in this direction must be reduced the linear heat cable detector shall be mounted on the bottom of the joists and the spacing of the detector on all runs measure at right angles parallel to the joists shall not exceed 50% of the smooth ceiling spacing, on runs the parallel both joists and wall the spacing shall not exceed 25%
On solid beam ceiling installations, in the case of beam construction, where the beams are 4” or less in the depth, the ceiling shall be treated the same as a smooth ceiling. If the beams project more than 4” below the ceiling, the spacing at right angles to the direction of beam travel shall not exceed 2/3 of the smooth ceiling spacing.
Parameters:
1.Complied with GB16280-2014 standard。
2.Temperature alert actions:85℃
3.100mm small size fire alarm functions
4.Detector type: unrecoverable cable line-type fixed temperature fire detector;
5.Working voltage: 24V±15%
6.Monitors current:<100mA
7.Power supply overload protection current: 200mA
8.Applicable temperature range: -40℃ ~ +50℃ (D)
9.Relative humidity:≤95% , without condensation
10.Status indicator: Normal operation---green light flashing
Alarm status---red light on
Fault status---yellow light on
11.Crust protection grade: IP66
Testing Linear Heat Detectors Cable
1.Fixed-temperature, rate-of-rise, rate-of-compensation, restorable line, spot type (excluding pneumatic tube type)
oHeat test shall be performed with a heat source per the manufacturer’s published instructions for the installed equipment, or other method shall be used that will not damage the non-restorable fixed temperature element of a combination rate-of-rise or fixed-temperature element detector.
2.Fixed-temperature, non-restorable line type (Protectowire)
oHeat test shall not be performed. Functionality shall be tested mechanically and electrically. Loop resistance shall be measured and recorded. Changes from acceptance test shall be investigated.