The detectors are photo-electronic detector uses a state of-the-art optical sensing chamber.
Product overview

The detectors are photo-electronic detector uses a state of-the-art optical sensing chamber. This detector is designed to provide open area protection and to be used with most security alarm control panel.


Product Features
Two LEDs on each detector provide local 360° visible alarm indication. They flash every six seconds indicating that power is applied and the detector is working properly. The LEDs latch on in alarm. LEDs will be off when a trouble condition exists indicating that the detector sensitivity is outside the listed limit. The alarm can be reset only by a momentary power interruption.
The detector that initiated the alarm condition will have its red LED and relays latched until reset by panel.
Heat detector and smoke & heat detector combine a photo electronic sensing chamber and a temperature heat detector.
Technical parameters

Operating Voltage Range 9 to 28 VDC Volts Non-polarized
Standby Current:  ≤200µA
Maximum Alarm Current (LED on)  ≤45mA
Alarm Relay Contact Ratings 2A@ 24V DC
Operating Humidity Range  ≤95%RH(40°C±2°C) Relative Humidity, Non-condensing
Operating Temperature Range -10°C to 50°C (14°F to 122°F)
Smoke Alarm Sensitivity 1.06±.26%FT
Temperature Alarm Sensitivity 57°C (135°F) A1R (only for with heat sensor)
Height 55 mm installed in Base
Diameter 103 mm