We supply whole fire alarm and suppression system include conventional fire alarm system, addressable fire alarm system, emergency light system, FM200 gas suppression system, fire pump, fire hose reel and cabinet.
Since 2005, Fire Alarm System And Fire Suppression System Manufacturer&Whole Solution Provider
Conventional Fire Alarm Control System LPCB Approved
4 Zone Fire Alarm Control Panel AW-CFP2166-4-8
The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler su
The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.
Main indication on main board
1.1Fire alarm indication
At the top area of the panel is the main display. When enter to fire alarm, the red FIRE LED lights. If the outputs:
Sounder/ Fire protection/ Fire routing did not disabled or have any faults, red ACTIVE LED light.
1.2Fault display on main board
Any fault occurs, General Fault indicator lights.
On the panel, main display area has 4 outputs: Sounder/ Fire protection/ Fire routing/ Fault routing, if all being wet mode and did not disabled, any fault indicates on the panel. Faults fall into short and open.
On the left, other faults include mains fault/ battery fault/ earth fault/ fuse fault/ system fault.
Mains fault: there is no mains power comes to panel. Pull mains plug up, check if wires connect hard. Or fuse is break on the EMI board. Of course, premise your lamp is lighting.
Battery fault: there is no power comes from batteries. Check the battery switch on, if wires connected well. Of course, premise you have got 2 batteries inside. If all these above are ok, batteries are too old to supply power, change them.
Earth fault: there are some points on PCBs contact to enclosure. Insure wires connected clearness.
Fuse fault: the fuse on power board broken. Get it out and put another one inside.
System fault: open the door, check if every zonal board has a green LED flashing organized. Or if your 4 bits DIP switches are dialed correctly.
1.3Disablement indication
The 4 outputs, if anyone disabled, corresponding “disable” lights and “General Disable” lights.
1.4Indication of operation
Except 4 outputs, we have another 4 buttons: Test/ Reset/ Evacuate/ Silence, when touch off, the LED belongs to lights and trigger corresponding outputs.
Product Features
4 Zone Fire Alarm Control Panel Specification
1. It is modularized design, the panel can expend from 1 zone to 32 zones easily.
2. It has 2 level control mode by a lock
3. It has 24VDC and 5VDC power supply output.
4. It has FIRE and FAULT signal output.
5. It has 2 general sounders output.
6. Each zone has 1 circuit detectors input
7. Each zone can be disable by a button.
8. It has RESET button to reset the panel.
9. It has SILENCE button to stop BUZZER and SOUNDERS.
10. It has EVACUATE button to start a manual fire alarm immediately.
11. It has battery low protection function, when battery voltage lower than 21VDC
battery will be cut off automatically until the mains power is on.
12. It has an optional GSM module for fire alarm by SMS
Technical parameters
AC INPUT
220VAC 50HZ
+10%
-15%
DC OUTPUT
24VDC typical
Voltage for MCU
5V for power board MCU, 3.3V for others
Current at 24VDC from PSE
450mA standby current
Maximum current from PSE
2A except batteries charge
Batteries current
1.85A maximum, current limited
Auxiliary output
24VDC +/- 10%, 100 mA max,
current limited, monitored
Batteries
2*12V/ 2.3Ah sealed lead acid gel,
self-regulated
2*12V/ 7Ah if needed
Battery replace Resistance
2Ω±10% if needed
Battery low-voltage protection
22.2V
Detectors connection allowed each zone
20 (except MCPs)
Zone alarm current
6mA minimum/ 27mA maximum
Sounder output
2*0.75A maximum
Fire protection
100mA maximum
Fire routing
100mA maximum
Fault routing
100mA maximum
Communication protocol
2 wires RS485 bus system
Relay contacts rating
Dry contacts (NO/NC) 1A @24VDC
EOL resistor for zone
6.8K 1W
EOL resistor for outputs
6.8K 1W
Fuse on power board
3A/ 250V glass tube fuse 20mm
Fuse on EMI board
1A/ 250V glass tube fuse 20mm
Environmental
Class A temperature range: -5 to 50°C
Humidity: 5 to 95% RH, non-condensing
Terminal blocks rating
All terminals rated for 12 to18 AWG
(0.75 to 2.5 mm2)