Conventional Fire Alarm Control System LPCB Approved
2 Zone Fire Alarm Control Panel AW-CFP2166-2
The AW-CFP2166 2 Zone series conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations
Product overview

The AW-CFP2166 series 2 Zone conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.

Product Features
2 Zone Fire Alarm Control Panel Features
1.Maximum number of Analogue Conventional Detector Inputs: 20 detectors each  zone
2.Available Options: 2-4 Zone and 6-8 Zone
3.outputs for Alarm devices: Includes 2 bells/fire relay/ fault relay
4.Auxiliary resettable power output: 24VDC/ 100mA limiting protection
5.Automatic power switchover: mains power and secondary power (from batteries)
6.Independent functional buttons with indication: User friendly interface for easy operation and recognition
7.Access levels to enter the panel
8.Fault supervision and notification: inputs, outputs, system, power, earth, fuse
9.Disablement: zones disablement 10.Evacuation: Fire drills to simulate fire alarm condition on panel
11.Silence: sounders and buzzer silence 12.Walk test: indicators check
Technical parameters

AC INPUT
 
220VAC 50/60Hz
+10%
    -15%
DC OUTPUT 24VDC typical
Voltage for MCU 5V for MCU
Current at 24VDC from PSE 450mA standby current
Maximum current from PSE 1A except batteries charge
Batteries current 1.85A maximum, current limited
 
Auxiliary output
24VDC +/- 10%, 100 mA max,
current limited, monitored
 
Batteries
2*12V/ 2.3Ah sealed lead acid gel,
self-regulated *
Battery low-voltage protection 21V
Detectors connection allowed each zone 20 (except MCPs)
Zone alarm current 6mA minimum/ 27mA maximum
Sounder output 2*0.75A maximum
Fire Relay 1A/30VDC maximum
Fault Relay 1A/30VDC    maximum
Communication protocol 2 wires RS485 bus system
EOL resistor for zone 6.8K 1W
EOL resistor for outputs 6.8K 1W
Fuse for AC Power 1 A/ 250V glass tube fuse 5 X 20mm
Fuse on DC Power 1A/ 250V glass tube fuse 5 X 20mm
 
Environmental
Class A temperature range: -5 to 50°C 
Humidity: 5 to 95% RH, non-condensing
 
Terminal blocks rating
All terminals rated for 12 to18 AWG
(0.75 to 2.5 mm2)

Download
BACK