Conventional Fire Alarm Control System LPCB Approved
1 Zone Fire Alarm Control Panel AW-CFP2166-1
The AW-CFP2166 series 1 Zone conventional fire alarm panel is the heart of the conventional fire alarm system, which can realize centralized control, can supply power to the detectors.
The AW-CFP2166 1 Zone series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
It is the heart of the fire automatic alarm system, which can realize centralized control,
can supply power to the detectors, manual call point, bell etc.
One zone of the panel can match with 20 pieces fire alarm system accessories.
Product Features
The AW-CFP2166 1 Zone fire alarm panel has the following characteristics:
Analogue conventional detector inputs: 20 detectors or MCPs maximum.
Smaller size and easier for installation, but all-around.
Maximum number of bells per CIE: 4 Bells.
2 relay-outputs: FIRE/FAULT.
High-capacity batteries: 12V2.3Ah*2, over 8h for stand-by use.
Automatic power switchover: mains power and stand-by power.
Succinct functional buttons: friendly user interface for easy operation and recognition.
Fault supervision and notification: inputs, sounder, mains/batteries.
Evacuation: man-made fire alarm condition on panel.
Silence: sounders and panel buzzer.
Extensible application for GSM: inform user anytime by mobile telephone.
Technical parameters
AC INPUT
220VAC 50/60Hz
+10%
-15%
DC OUTPUT
24VDC typical
Voltage for MCU
5V
Current @ 220VAC
standby current ≤250mA
Maximum current
1A
Batteries current
750mA maximum, current limited
Batteries
2*12V/ 2.3Ah sealed lead acid gel, self-regulated
Battery low-voltage protection
22.2V
The maximum and minimum electrical ratings for each input and output
Detectots / zone lines: 21V-26V Sounder1 and sounder2 lines:21-26.2V
Fire protection/Fire routing/Fault routing lines:21-26.2V
Max points (detector and MCP) per CIE
20 detectors and 10 MCPs
Zone alarm current
6mA minimum/ 27mA maximum
Sounder output
2*0.3A maximum
Relay contacts rating
Dry contacts (NO/NC) 1A @24VDC
EOL resistor for zone and outputs
6.8K 1W
Fuse on EMI board
2A/ 250V Ceramic slow blow fuse 5*20(mm)
Environmental
Class A temperature range: -5 to 50°C
Humidity: 5 to 95% RH, non-condensing
Terminal blocks rating
All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2)