Packaged fire pump system
Deluge Alarm Valve/Rain Alarm Valve
Deluge valve can be opened in a flash, let the water into the valve cavity into the water distribution pipe network automatic valves.
Product overview
Deluge valve automatic water supply control valve, with the aid of auxiliary operation institutions to open pipeline system of water supply to the deluge system or preaction system closed pipeline system of a kind of automatic water supply control valve, the valve electric, mechanical or other way to open it.

Product Features
Features:

Deluge valve group is mainly composed of water control valves, butterfly valves, deluge valve, manual emergency device, automatic water valve, drain valves, water supply side cavity pressure gauges, control, etc.

When there is a fire, the fire linkage motion control module, open the solenoid valve, by controlling the export of cavity through to atmospheric pressure. Due to the pressure-relief devices used to control the import of cavity effect, to control the pressure inside the cavity fell sharply, when the control cavity pressure is lower than the pressure of water supply to a certain value, the function in the bottom of the valve cover upward force is greater than the downward force on leverage on the disc. The deluge valve disc is open water supply pressure, the water flows into the fire extinguishing system side, control cavity pressure gauge installed in the protection zone of fire detection system are the same that deluge valve disc drive system control.

It can be electric, hydraulic (wet), pneumatic (dry).


Deluge alarm valve main form:


Technical parameters
Parameters:

Model No. AW-DV100/150/200
Pipe Diameter 100mm/150mm/200mm
Work pressure 1.2~1.6MPa
Seal pressure test 2.4~3.2MPa
Scope of supply pressure 0.14~1.6MPa
Pipe network pressure range 0.3~0.5MPa (Dry)
Alarm performance DN100, 150 alarm within 15 s; DN200 alarm within 60 s
Alarm inlet pressure ≥0.05MPa


 
Download