Since 2005, Fire Alarm and Suppression System Manufacturer & Whole Solution Designer,
We supply whole fire alarm and suppression system include conventional fire alarm system, addressable fire alarm system, emergency light system, FM200 gas suppression system, fire pump, fire hose reel and cabinet.
  • Home
  • Products
    The AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 24 standard. 
    Asenware FP300 series is a LPCB addressable fire alarm system with one loop of 324 addressable points, comply with EN 54 standard.
    Smoke Detector is a device that senses smoke, typically as an indicator of fire.
    ASENWARE Heat Detector is photo-electronic detector using a state-of-the-art optical sensing chamber. 
    ASENWARE Smoke and Heat Detector is photo-electronic detector using a state-of-the-art optical sensing chamber. 
    Voice Evacuation Control Panel and Speakers
    Fire Telephone is a new fire special communications equipment when the fire accident.
    ASENWARE units are designed for the purpose of alerting audio and visual awareness to an emergency situation.
    Conventional Manual Call Point is designed for conventional fire alarm system to report fire in emergency condition 
    Fire Bell is the fire alarm, a fire alarm device, generally used for more staff in public areas
    ASENWARE Reflex Beam Smoke Fire Detector, being designed for fire prevention, is a long interval one and used with the fire alarm controller
    ASENWARE Flame Detector provides a new generation of flame detection capability and technical standards
    Fire Proof Cable is used where critical circuits need to function to keep safety equipment running even when exposed to extreme heat or fire. 
    AW-AFP2189 is a new type of analog fire alarm control panel which has 324 alarm control points 
    ASENWARE Fire Pump Series provide fire departments or private users with the ability to pump from any water source.
    ASENWARE FM200 (Heptafluoropropane, HFC-227ea) fire extinguishing system is a gas fire, automatic control and fire detection.
    ASENWARE Explosion-Proof Series is a indispensable equipment in explosion-proof fire alarm system.
    ASENWARE Centralized Monitoring Emergency Luminaire System is designed for managing, monitoring and controlling emergency lights automatically. 
    ASENWARE Other Fire Alarm Accessories
  • Project
  • Newsroom
  • Company
  • Contact
LPCB Addressable Fire Alarm Sy...
Home > Products > LPCB Addressable Fire Alarm System
LPCB Addressable fire alarm system 32 zone control panel AW-FP300
The purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualit...
  • The purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance.
    The AW-FP300 panel is an addressable fire detection panel with 1 loop of 324 addressable points and expansion capabilities. It is compatible with other peripherals made by ASENWARE with its own protocol.
  • Features:
    The AW-FP300 single loop 32 zone fire alarm control panel offers the following features: 
    1. Up to 324 addresses on one loop
    2. An easy to read, 4.3'' color screen LCD with a resolution of 480×272
    3. Zone indication and control panel(ZCP) for 32 zones gives a quick indication of the location of an alarm
    4. Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation
    5. An independently programmable conventional sounder circuit output
    6. Integral power supply and battery
    7. Integral printer
    8. Flexible and intuitive cause and effect programming on front panel
    9. Zone test, point test and module start/stop testing facilitate the commissioning
    10. U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance
    11. Hierarchy management with three access levels 
    12. Anti-tamper protection by a key lock
    13. CAN bus for interconnection of up to 20 FACPs and RS485 for connection with up to 30 fire indicating panels per FACP
  •  Power supply 
    Mains supply  230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A 
    Mains fuse  T3.15AL250V 
    Operating voltage  18.5 ~ 30VDC 
    Recommended mains cable  Screened or standard/black mains cable, cable size 0.75mm2 
    Power rating  Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A 
    Max. charging current  1.2A 
    Max. battery supply current  4A (when the Mains is disconnected) 
    Battery capacity, type and recommended model  Max. capacity 2×12V/17Ah; Min. capacity 2×12V/12Ah 
    VRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic) 
    Max. internal resistance of battery  1.5Ω
    Battery fuse  F8AL250V 
    Recommended battery cable  14AWG 
    Quiescent current (full loaded)  < 0.4A 
    Outputs 
    S.C. Out (+, -)  Output voltage  18.5 ~ 30VDC 
    Max. output current  0.5A 
    Fuse rating  F1AL250V 
    End of line resistor  4K7 
    Recommended type of cable  Plain unscreened cable, 1.5mm2 
    Cable diameter  1mm2 ~2mm2 
    Transmission distance  ≤1500m 
    Max. number of sounders @50mA  20 
    F.P.E. Out (+, -) 
    F.A. Out (+, -) 
    Output voltage  18.5 ~ 30VDC 
    Max. output current  0.5A 
    Fuse rating  F1AL250V 
    End of line resistor  4K7 
    Recommended type of cable  Plain unscreened cable, 1.5mm2 
    Cable diameter  1mm2 ~2mm2 
    Transmission distance  ≤1500m 
    Fault Out 
    (NC, COM, NO) 
    Contact capacity  30VDC@2A, 125VAC@0.5A 
    Recommended type of cable  Plain unscreened cable, 1.5mm2 
    Cable diameter  1mm2 ~ 2mm2 
    24VK (+, -)  Output voltage  18.5 ~ 30VDC 
    Max. output current  0.6A 
    Fuse rating  F1AL250V 
    Recommended type of cable  Plain unscreened cable, 1.5mm2 
    Cable diameter  1mm2 ~2mm2 
    Input 
    Class change (+, -)  Input mode  Passive 
    Cable resistance  ≤500Ω
    Recommended type of cable  Plain unscreened cable, 1.5mm2 
    Cable diameter  1mm2 ~2mm2 
    Loop 
    Loop Out (+, -) 
    Loop In (+, -) 
    Output voltage  16.5 ~ 30VDC, pulse 
    Output current  0 ~0.3A 
    Loop type  Class A 
    Recommended type of cable  Screened or unscreened twisted-pair, 1.5mm2 
    Transmission distance  ≤1000m 
    Cable diameter  1mm2 ~2mm2 
    Network communication 
    RS-485  Max. number of FIPs  30 
    Transmission rate  9600 bps 
    Recommended type of cable  Screened or unscreened twisted-pair, 1mm2 
    Transmission distance  ≤1000m 
    Cable diameter  1mm2 ~5mm2 
    CAN  Max. number of panels  20 
    Transmission rate  Optional: 10K, 20K, 50K and 100K bps 
    Recommended type of cable  Screened or unscreened twisted-pair, 1mm2 
    Transmission distance  ≤1000m 
    Cable diameter  1mm2 ~5mm2 
    Physical dimensions 
    Approx. Dimensions of the panel (W×H×D)  430×560×170mm 
    Approx. weight (without battery)  14kg 
    Operating conditions 
    Temperature range: 0°C~45°C; Max relative humidity: 95% (40°C ±2°C, no condensation) 